Bergerak dalam bidang jasa alat - alat elektronik dan pendingin terutama pendingin industri service chiller di cikarang service water chiller service cold room service cold storage service air dryer/ meliputi kawan indutri service chiller bekasi ,service chiller di cikarang cibitung jababeka cikarang hundai cikarang Delta silicon cikarang , ejiep cikarang

Hubungi Kami Via Whatsapp


CITRA TEKNIK - 081310401011

sebagai teknisi kita harus bisa melakukan pengecekan  unit ac apa lagi sekarang setiap ac sudah ada kode error nya masing masing berikut s...

cara mencari kode error ac inverter panasonik

sebagai teknisi kita harus bisa melakukan pengecekan 
unit ac apa lagi sekarang setiap ac sudah ada kode error nya masing masing
berikut satu contoh melakukan pengecekan kode error ac inverter Panasonik
Cara cari kode error ac inverter panasonik..

Arahkan remote pada unit.... inverter panasonic
Tekan dan tahn tombol "check",nanti pada remote akan muncul kombinasi huruf dan angka.
Selanjutnya cari kodenya dengan menekan tombol up/down timer,
Jika terdengar bunyi beep panjang,itulah kode kombinasi huruf dan angka,
Cocokan pada kode kerusakan di chasing indoor,
Tinggal exsekusi seseuai.. kode error



atau perhatikan kode error ac inverter panasonik di bawah ini

Diagnosis display = H00
Abnormality / Protection control = No abnormality detected
Abnormality Judgement =
Emergency operation = Normal operation
Primary location to verify =

Diagnosis display = H11
Abnormality / Protection control = Indoor / Outdoor abnormal communication
Abnormality Judgement = > 1 min after starting operation
Emergency operation = Indoor fan operation only
Primary location to verify = • Internal / external cable connections • Indoor / Outdoor PCB

Diagnosis display = H14
Abnormality / Protection control = Indoor intake air temperature sensorabnormality
Abnormality Judgement = Continue for 5 sec.
Emergency operation =
Primary location to verify = • Intake air temperature sensor (detective or disconnected)

Diagnosis display = H15
Abnormality / Protection control = Outdoor compressor temperature sensor abnormality
Abnormality Judgement = Continue for 5 sec
Emergency operation =
Primary location to verify = Compressor temperature sensor (detective or disconnected)

Diagnosis display = H16
Abnormality / Protection control = Outdoor Current Transformer open circuit
Abnormality Judgement =
Emergency operation =
Primary location to verify = • Outdoor PCB • IPM (Power transistor) module

Diagnosis display = H19
Abnormality / Protection control = Indoor fan motor mechanism locked
Abnormality Judgement = 7 times occurance continuously
Emergency operation =
Primary location to verify = • Indoor PCB • Fan motor

Diagnosis display = H23
Abnormality / Protection control = Indoor heat exchanger temperature sensor abnormality
Abnormality Judgement =
Emergency operation = O (Cooling only}
Primary location to verify = • Heat exchanger temperature sensor (detective or disconnected)

Diagnosis display = H24
Abnormality / Protection control = Indoor heat exchanger temperature sensor 2 abnormality
Abnormality Judgement = Continue for 5 sec.
Emergency operation =
Primary location to verify = • Heat exchanger temperature sensor (detective or disconnected)

Diagnosis display = H27
Abnormality / Protection control = Outdoor intake air temperature sensor abnormality
Abnormality Judgement = Continue for 5 sec.
Emergency operation = O
Primary location to verify = • Outdoor temperature sensor (detective or disconnected)

Diagnosis display = H28
Abnormality / Protection control = Outdoor heat exchanger temperature sensor abnormality
Abnormality Judgement = Continue for 5 sec.
Emergency operation = O
Primary location to verify = • Outdoor heat exchanger temperature sensor (detective or disconnected)

Diagnosis display = H30
Abnormality / Protection control = Outdoor discharge air temperature sensorabnormality
Abnormality Judgement = Continue for 5 sec.
Emergency operation =
Primary location to verify = • Outdoor temperature sensor (detective or disconnected)

Diagnosis display = H33
Abnormality / Protection control = Indoor / Outdoor wrong connection
Abnormality Judgement =
Emergency operation =
Primary location to verify = • Indoor / Outdoor supply voltage

Diagnosis display = H38
Abnormality / Protection control = Indoor / Outdoor mismatch (brand code)
Abnormality Judgement =
Emergency operation =
Primary location to verify =

Diagnosis display = H50
Abnormality / Protection control = Ventilation motor abnormality
Abnormality Judgement = 7 times occurance continuously
Emergency operation =
Primary location to verify = • Indoor PCB • Ventilation motor

Diagnosis display = H51
Abnormality / Protection control = Nozzle lock abnormality
Abnormality Judgement = 2 times occurance continuously
Emergency operation =
Primary location to verify = •Nozzle

Diagnosis display = H52
Abnormality / Protection control = Limit switch abnormality
Abnormality Judgement =
Emergency operation =
Primary location to verify = • Indoor PCB

Diagnosis display = H97
Abnormality / Protection control = Outdoor fan motor mechanism locked
Abnormality Judgement = 2 times occurance within 30 minutes
Emergency operation =
Primary location to verify = • Indoor PCB • Fan motor

Diagnosis display = H98
Abnormality / Protection control = Indoor high pressure protection
Abnormality Judgement =
Emergency operation =
Primary location to verify = • Air filter dirty • Air circulation short circuit

Diagnosis display = H99
Abnormality / Protection control = Indoor heat exchanger anti-freezing protection
Abnormality Judgement =
Emergency operation =
Primary location to verify = • Insufficient refrigerant • Air filter dirty

Diagnosis display = F11
Abnormality / Protection control = Cooling / Heating cycle changeover abnormality
Abnormality Judgement = 4 times occurance within 30 minutes
Emergency operation =
Primary location to verify = •4-way valve • V-coil

Diagnosis display = F90
Abnormality / Protection control = PFC control
Abnormality Judgement = 4 times occurance within 10 minutes
Emergency operation =
Primary location to verify = • Voltage at PFC

Diagnosis display = F91
Abnormality / Protection control = Refrigerantion cycle abnormality
Abnormality Judgement = 2 times occurance within 20 minutes
Emergency operation =
Primary location to verify = • No refrigerant (3-way valve is closed)

Diagnosis display = F93
Abnormality / Protection control = Compressor rotation failure
Abnormality Judgement = 4 times occurance within 20 minutes
Emergency operation =
Primary location to verify = •Compressor

Diagnosis display = F95
Abnormality / Protection control = Cool high pressure protection
Abnormality Judgement = 4 times occurance within 20 minutes
Emergency operation =
Primary location to verify = • Outdoor refrigerant circuit

Diagnosis display = F96
Abnormality / Protection control = IPM (power transistor) overheating protection
Abnormality Judgement = 4 times occurance within 30 minutes
Emergency operation =
Primary location to verify = • Excess refrigerant • Improper heat radiation • IPM (Power transistor)

Diagnosis display = F97
Abnormality / Protection control = Outdoor compressor overheating protection
Abnormality Judgement = 4 times occurance within 10 minutes
Emergency operation =
Primary location to verify = • Insufficient refrigerant • Compressor

Diagnosis display = F98
Abnormality / Protection control = Total running current protection
Abnormality Judgement = 3 times occurance within 20 minutes
Emergency operation =
Primary location to verify = • Excess refrigerant • Improper heat radiation

Diagnosis display = F99
Abnormality / Protection control = Outdoor Direct Current (DC) peak detection
Abnormality Judgement = 7 times occurance continuously
Emergency operation =
Primary location to verify = • Outdoor PCB • IPM (Power transistor) • Compressor